- Product Features
-
- Stainless steel tube protects the fiber with high tensile strength
- Small cable diameter and light weight, with low additional load on towers
- The optical unit provides appropriate primary fiber excess length
- Slightly lower resistance to tension, torsion, and lateral pressure
- Structural Parameters
-
- Fiber: G652D/G655 and other types;
- Fiber count range: 2-48 fibers
- Protection tube: stainless steel tube;
- Diameter: 1.5-6 mm
- Stranded single wires: aluminum-clad steel / aluminum alloy / aluminum rod;
- Diameter: 1.5-6 mm
- Max. outer diameter: 18 mm;
- Max. cross-section: 200 mm²
- Mechanical Performance
-
- Standard: DL/T 832-2016
- Max. tensile strength (RTS): 280 kN;
- Max. crush load: 2200 N/100 mm
- Max. short-circuit current capacity: 100 kA²·s (40℃~200℃)
- Min. bending radius: dynamic 20D;
- static 15D (D is the OPGW cable diameter)
- Environmental Performance
-
- Installation temperature range: -10℃ to +50℃
- Operating and storage temperature range: -40℃ to +65℃
- Fiber Characteristics
| Fiber Type | Fiber Attenuation (dB/km) @850 nm | Fiber Attenuation (dB/km) @1300 nm | Fiber Attenuation (dB/km) @1310 nm | Fiber Attenuation (dB/km) @1550 nm | Bandwidth (MHz·km) @850 nm | Bandwidth (MHz·km) @1300 nm | Polarization Mode Dispersion (ps/km), single fiber | Polarization Mode Dispersion (ps/km), link value (M=20, Q=0.01%) |
| G652D | — | — | ≤0.35 | ≤0.21 | — | — | ≤0.20 | ≤0.10 |
| G655 | — | — | — | ≤0.22 | — | — | ≤0.20 | ≤0.10 |
| 50/125μm | ≤3.0 | ≤1.0 | — | — | ≥600 | ≥1200 | — | — |
| 62.5/125μm | ≤3.5 | ≤1.0 | — | — | ≥200 | ≥600 | — | — |
- Specific Models and Technical Parameters
| Model | Cable Structure | Max. Fiber Count (cores) | Aluminum-Clad Steel Cross-Section (mm²) | Outer Diameter (mm) | Mass per Unit Length (kg/km) | Rated Breaking Load (kN) | DC Resistance at 20℃ (Ω/km) | Allowable Short-Circuit Current Capacity (40-200℃ kA²·s) |
| OPGW-24B1.3-40-[51;9] | 6/3.0/20AS, optical unit 1/3.0 | 24 | ≈40 | 9.0 | ≤304 | ≥51 | ≤2.10 | ≥9 |
| OPGW-24B1.3-50-[58;11.5] | 6/3.2/20AS, optical unit 1/3.2 | 24 | ≈50 | 9.6 | ≤345 | ≥58 | ≤1.82 | ≥11.5 |
| OPGW-48B1.3-70-[77;24] | 6/3.8/20AS, optical unit 1/3.8 | 48 | ≈70 | 11.4 | ≤475 | ≥77 | ≤1.30 | ≥24 |
| OPGW-48B1.3-70-[42;38] | 6/3.8/40AS, optical unit 1/3.8 | 48 | ≈70 | 11.4 | ≤340 | ≥42 | ≤0.70 | ≥38 |
Note: Other fiber counts, fiber types, and stranding types are all customizable.
- Mechanical and Environmental Performance Test Standards
| Test Item | Test Method | Acceptance Criteria |
| Tensile | GB/T 7424.2-E1 | Load: varies with cable structure; sample length: no less than 10 m, link no less than 100 m; duration: 1 min; 40% RTS: no significant fiber strain (≤0.01%) and no significant additional attenuation (≤0.03 dB); 60% RTS: fiber strain ≤0.25%, additional attenuation ≤0.05 dB (after load removal, no significant residual additional attenuation, ≤0.03 dB) |
| Crush | GB/T 7424.2-E3 | Load: per the table above, tested at 3 points; duration: 10 min; After the test, the additional attenuation of the single-mode fiber at 1550 nm shall not exceed 0.05 dB per fiber, and the OPGW shall show no mechanical damage |
| Water Penetration | GB/T 7424.2-F5 | Duration: 1 hour; sample length: 0.5 m; water head: 1 m; No water penetration |
| Temperature Cycling | GB/T 7424.2-F1 | Sample length: no less than 500 m; temperature range: -40℃ to +70℃; cycles: 2; soak time: no less than 12 h; After the test, the additional attenuation of the single-mode fiber at 1550 nm shall not exceed 0.1 dB |
- Packaging and Delivery Requirements
-
- Packaging: standard drums
- Delivery length: 2/3 km, also customizable per customer requirements